Bio Fuel Generating Set
Products & Services
Information
Bio Diesel Generator Set
Engine runs on Bio Fuel - UCO with Red diesel start and run-down switch facility automatically, locally or remotely
Engine automatically switches from Red Diesel on start up to Bio Fuel when operating parameters have been met.
If load drops or shutdown is initiated, the reverse switch to Red Diesel is initiated
Export of power - only in Bio Fuel operating mode
Containerised enclosure suitable for plant room mounting
Internal ceiling mounted lagged exhaust with aluminium and thermal cladding
Engine cooling system heats UCO in storage tank, via plate heat exchanger.
Excess engine heat removed by blast air coolers
LV generation transformed to HV for site usage by separate transformer.
G&M Tex supplied G59/3 compliant plant room tripping control panel and display